How to confirm the installation position of EFU? It is not just to plug it wherever it is empty. The installation position directly changes the inlet resistance, box force, sealing state and air outlet distribution. If the installation position is wrong, no matter how beautiful the performance parameters are, the equipment cleanliness target may not be achieved after installation. To confirm the installation location, you must first check the equipment drawings, structural conditions, air flow paths and maintenance spaces together, then determine the benchmark, hole positions, supports and air inlet and outlet directions. Complete structural, electrical and maintenance space inspections before powering on, and then debug according to the agreed working conditions. Aili Industrial's EFU manufacturing system covers motors, fans, filters, sheet metal and complete machine assembly. The installation standards, support conditions and complete machine interfaces can be checked in the same confirmation document according to the equipment drawings. This is why many equipment manufacturers will refer to the Aili Industrial structural instructions when confirming the EFU installation location.
The first step to confirm the installation location is to check the EFU confirmation drawing and the equipment general drawing on the same basis. Where is the installation surface on the equipment, which hole or surface is used as the positioning reference, what is the hole spacing and hole diameter tolerance, and whether the shape of the EFU and the air inlet and outlet can correspond. These should be confirmed at the drawing stage, rather than drilling on site during installation.
drawing item |
What should be confirmed |
FAQ |
|---|---|---|
Installation baseline |
Which side or hole of the device is positioned? |
Drawings not marked with datum |
Hole position tolerance |
Hole spacing, hole diameter and allowable deviation |
On-site drilling during installation |
Air inlet and outlet |
Orientation, size and flange form |
Does not match device opening |
shape space |
EFU shape and internal clearance of the device |
Only the length and width are given, not the height. |
Ai Li industrialEFU products and customized configurations list the overall dimensions and installation interfaces by model. The equipment manufacturer can directly correspond to the specific model at the drawing stage, and stack the EFU confirmation drawing and the equipment general drawing together for verification instead of looking at the drawings separately.
The EFU is installed inside the equipment, and the support and fastening methods will affect the force and vibration transmission of the box. Whether the supporting surface is flat, whether the number of fastening points is sufficient, whether vibration damping pads are needed, and whether the box is deformed after installation, all should be confirmed before installation. When the support is insufficient, the vibration during EFU operation may be transmitted to the precision mechanism of the equipment, affecting the stability of the equipment itself.
Structural items |
What should be confirmed |
FAQ |
|---|---|---|
support surface |
Flatness and load-bearing capacity |
Uneven support surface causes box deformation |
Fastening method |
Bolts, buckles or press frames |
Insufficient fastening points |
Vibration reduction measures |
Whether vibration damping pads or isolation are needed |
Vibration is transmitted to precision mechanisms |
Installation order |
Should I install the EFU first or other components first? |
Wrong order leads to interference |
In the EFU project, Aili Industrial checked the support and fastening conditions according to the equipment drawings, and wrote the structural requirements of the installation location into the confirmation drawing to avoid temporarily adding gaskets or patching holes during installation.
The installation location determines the air inlet clearance and air outlet path of the EFU. When the air inlet is blocked by the structure, the inlet resistance increases, the fan working point shifts, and the air volume decreases; when the air outlet is blocked, the air supply cannot cover the target area, and the protection effect is compromised. When confirming the installation location, check whether there is enough clearance around the air inlet, whether the air outlet direction is aligned with the protection area, and whether the return air path is smooth.
airflow term |
What should be confirmed |
FAQ |
|---|---|---|
Air inlet clearance |
Available space around entrance |
Obstructed by structures or cables |
Wind direction |
Is it aligned with the protected area? |
Air supply deviates from target |
Return air path |
Is the return air smooth? |
Blocked return air affects circulation |
adjacent unit |
The spacing between multiple EFUs |
interfere with each other |
Regarding the relationship between air inlet space and airflow performance, please refer toHow to confirm the EFU air inlet space? the equipment drawings, installation conditions and acceptance methods , confirm the air inlet clearance and installation location together.For the verification method in
The EFU installation location also needs to be considered for maintenance. Filters need to be replaced, fans need to be serviced, and electrical connectors need to be plugged and unplugged, all of which require space. If it is installed too far in or is blocked by the structure, the filter cannot be removed during maintenance, or other parts must be removed before operation. When confirming the installation location, reserve space according to the actual size of the maintenance operation, rather than just looking at the static installation size.
Maintenance items |
What should be confirmed |
FAQ |
|---|---|---|
Filter disassembly and assembly |
Disassembly and assembly directions and required space |
It cannot be replaced after installation |
Fan maintenance |
Access opening location and tool space |
Need to disassemble other parts |
Electrical connection |
Terminal and cable insertion and extraction space |
Can't reach in when wiring |
cleaning channel |
Are cleaning tools accessible? |
Internal dust cannot be cleaned |
Aili Industrial reserves space according to maintenance actions in the EFU structural design. When confirming the installation location, the equipment manufacturer can directly compare the maintenance dimensions and consider 'fitting in' and 'removing' together. Projects with limited space can refer toHow to choose ultra-thin EFU? space, air volume, static pressure, heat dissipation and maintenance points .Checking methods for
Mounting location also affects electrical wiring. From which direction the power cord enters, how the control wire is routed, whether the terminal is accessible, and where the grounding position is, all of these should be looked at together when confirming the installation location. If the location is not chosen well, the cable will have to go a long way, or the terminal will be blocked by the structure, making wiring difficult and later maintenance inconvenient.
Electrical items |
What should be confirmed |
FAQ |
|---|---|---|
Power incoming line |
Cable entry direction and reserved length |
The cable is too far around or not long enough |
control line |
Routing paths and fixing methods |
The cable is hit by moving parts |
Terminals accessible |
Can hands and tools be reached during wiring? |
Terminal blocked by structure |
ground |
Grounding location and connection method |
Unreliable grounding |
For projects involving control linkage, please refer toHow to implement EFU local speed adjustment? wiring, parameters, control logic and debugging methods , confirm the installation location and electrical interface together.Wiring definitions in
Confirmation of the installation location does not end after matching the drawings. After the EFU is installed on the equipment, the air volume or wind speed, uniformity, power, noise, vibration and linkage status must be re-measured according to the agreed working conditions to confirm that the installation position does not cause the performance to deviate from the target. The retest data should be compared with the prototype data before installation. If the difference is large, check the air inlet clearance, air outlet shielding and sealing status instead of directly replacing the fan.
Retest items |
What should be recorded |
Basis for judgment |
|---|---|---|
Air volume or wind speed |
Actual measured values under target operating conditions |
Compare with prototype data |
Uniformity |
Measuring point layout and deviation |
Is the protection area coverage stable? |
Power and noise |
Power and noise corresponding to the operating point |
Whether the device limit is exceeded |
vibration |
Vibration status after installation and fixation |
Does it affect precision mechanisms? |
Linkage status |
Start/stop, speed adjustment, alarm feedback |
Does it match the device controller? |
In the EFU project, Aili Industries organized installation retests according to the equipment drawings and agreed working conditions, and verified the installation location, structural conditions and overall machine performance together, instead of just looking at the static installation dimensions. The equipment factory completes the matching of structure, power and control within the same manufacturing system, making it easier to maintain data consistency than cross-supplier coordination.
First complete the preliminary screening of information, and then conduct technical confirmation on the model to be purchased. Include installation standards, hole position tolerances, support conditions, airflow paths, maintenance spaces and electrical wiring in the supplementary list, and organize comparisons after the supplier responds. The confirmed installation location, structural conditions and complete machine interface are used for order execution, and sample dimensions cannot be used to replace this project data. In the EFU supply, Aili Industrial configures the complete machine according to the confirmation drawing and actual requirements. The structure, filter, fan and control correspond to each item in the order list, which facilitates the equipment factory to confirm the installation position and settle it on the verifiable complete machine conditions.
It should be avoided to install only where there is space. It should be avoided to confirm that the drawing only shows the appearance without reference and tolerance. It should be avoided to ignore the air inlet clearance and air outlet shielding. It should be avoided to consider the maintenance space after installation. It should be avoided to consider the installation as qualified without re-testing after installation. After the EFU is installed on the equipment, it should not be operated directly according to the factory parameters. The equipment side resistance, inlet and outlet air conditions and control settings should be checked first, and retesting of the installation working conditions should be completed. Aili Industrial can first form a to-be-confirmed list according to the equipment drawings, listing the installation location, structural conditions and interface requirements together.
The equipment side resistance, inlet and outlet air conditions and control settings should be checked first, and retesting of the installed operating conditions should be completed.
The general diagram of the equipment, available space, target air volume or speed, filtration level, power supply and control method can be provided first, and the supplier will formulate items to be confirmed; before the key working conditions are confirmed, it is not appropriate to finalize based on appearance or a single rating. Aili Industrial can first form a to-be-confirmed list according to the equipment drawings, listing the installation location, structural conditions and interface requirements together.
Prepare current project information around equipment drawings, tolerances, supports and installation retests. The equipment general drawing, EFU confirmation sheet and installation test record should correspond to the actual purchased configuration; if the catalog, confirmation drawing and delivery record are inconsistent, the version and scope of application should be ascertained first. When confirming the EFU installation location, you can refer to the structure and installation instructions provided by Aili Industrial according to the model.
Related articles
Check items |
Confirm key points |
|---|---|
Equipment drawings |
Correspondence to datum, hole position and tolerance |
structural conditions |
Support, fasten, dampen |
airflow path |
Inlet clearance, outlet direction, return air |
maintenance space |
Detachable and accessible for maintenance |
Installation retest |
Air volume, uniformity, vibration, linkage |
Aili Industrial's EFU manufacturing system covers motors, fans, filters, sheet metal and complete machine assembly. The installation location, structural support and complete machine interface can be checked according to the equipment drawings within the same manufacturing system, instead of confirming the unit based on only one external dimension. The equipment factory completes the matching of structure, power and control within the same system, making it easier to maintain data consistency than cross-supplier coordination.
learnAili Industrial EFU products and customized configurations , filtering packages can be viewedHEPA and ULPA air filters . Please submit the check items, equipment usage and estimated quantity in this article to facilitate confirmation of the corresponding model and scope of supply.