FFU equipped with ULPA ultra-high efficiency filter

Aili Industrial FFU supporting ULPA ultra-high efficiency filter is installed at the filtering position of the fan filter unit and matches the FFU box, fan and fixed structure. It can be configured according to module size, operating air volume, allowable resistance and replacement method, and can be used for new clean projects, equipment matching and replacement of original FFU filters.
Status:
Quantity:

FFU equipped with ULPA ultra-high efficiency filter

Unit size matching | Air volume and resistance confirmation | New machine matching and replacement customization

Aili Industrial FFU is equipped with ULPA ultra-high-efficiency filter for particle filtration in the fan filter unit. U15, U16 or U17 configurations can be confirmed according to project requirements.

Product selection also considers the FFU box size, fan operating capacity, installation sealing and maintenance methods. It can be configured together with the Aili Industrial FFU, or the replacement parts solution can be evaluated based on the drawings and operating parameters of other existing units.

Get supporting specifications → Submit FFU model and size →

name

content

name

content

Supporting equipment

FFU fan filter unit

filter level

U15, U16, U17, confirm by model

Product size

Configuration according to unit installation interface

Filter material selection

fiberglass or PTFE

Install seal

Gasket or liquid tank, confirm according to structure

Performance matching

Air volume, resistance and fan operating point

Replacement method

Confirm according to the disassembly and assembly structure of the unit

Matching form

New machine matching, original machine replacement, non-standard customization

Features

Configure according to FFU installation size

Confirm the outer frame size, thickness, tolerance and sealing position according to the installation position of the unit filter. The size of the FFU module may be different from the actual size of the filter. When purchasing, please refer to the installation drawing or original filter size as the basis.

Match the fan operating conditions

Confirm the resistance of the filter at the designed air volume, and check the fan operating point in combination with other resistances of the FFU. Filter selection needs to take into account both the initial operation and the air supply demand after the resistance increases in the later period.

Cooperate with unit replacement structure

According to the upper disassembly, lower disassembly or other maintenance methods, confirm the filter fixed position, removal path and operating space, so that the product corresponds to the unit maintenance structure.

Support original unit replacement

The replacement configuration can be checked based on the old filter nameplate, box drawings and actual operating parameters. When upgrading the level, confirm whether the original fan and control conditions are suitable.

Product technical parameters

Parameter items

Product configuration or confirmation content

Product name

FFU equipped with ULPA ultra-high efficiency filter

Supporting units

Aili Industrial FFU or other FFU confirmed by the interface

filter level

U15, U16, U17, confirmed according to product test results

filter material

Glass fiber or PTFE, confirmed according to process and performance requirements

Filter element structure

Configuration according to installation space, air volume and resistance

Overall dimensions

Width W × Height H × Thickness D, confirm according to the installation position

Rated air volume

Matches the design air volume of a single FFU

initial resistance

Provide data for corresponding models under specified air volume

final resistance condition

Confirmation of project maintenance requirements and fan capacity

Sealing method

Gasket seal or tank seal

fixed structure

Press fasteners, supporting frames or other unit structures to confirm

Protection configuration

Net protection and accessories are confirmed upon request

Airflow direction

Install according to product identification and unit air flow path

Testing data

Efficiency, scanning leak detection and agreed delivery documents

The specific size, air volume, resistance and configuration are subject to the corresponding model specifications and confirmed drawings.

FFU module size and filter size

The nominal size of the FFU module cannot be directly used as the filter processing size. The box frame, supporting structure and installation clearance will affect the filter dimensions.

Check items

Confirm content

Unit module size

Installation dimensions of FFU on the ceiling or equipment

Filter frame size

Width, height and thickness required for actual installation

Effective air outlet area

The air outlet area after deducting the frame and occlusion

Sealing contact surface

Corresponding installation position of gasket or liquid tank

Fixation and support

Supporting surface, pressing position and mechanical limit

maintenance space

Access paths and clearances required to remove the filter

When customizing or replacing, it is recommended to provide the FFU model, filter size diagram and installation location photos.

Target wind speed and operating air volume

The face wind speed that FFU needs to achieve should be converted into operating air volume based on the effective air outlet area.

Operating air volume (m³/h) = target average surface wind speed (m/s) × effective air outlet area (m²) × 3600

This conversion is used to confirm air supply requirements. The final air volume and wind speed should be verified through actual measurement, and the measurement location and method should be clearly defined.

Operational requirements

Conditions to be checked

Target surface wind speed

Specified average wind speed and measurement conditions

Single operating air volume

The processing air volume corresponding to the effective air outlet area

Wind speed distribution

The influence of fan, box and filter element configuration on air output

Speed ​​range

Can control settings cover actual operating requirements?

Post run

Can the required air supply volume be maintained after the resistance increases?

ULPA filter matches FFU fan

After replacing or upgrading the filter, the unit resistance may change. The original speed or air volume at the control setting may also change accordingly.

When selecting, you should check:

Filter resistance: corresponds to the initial resistance under the design air volume and the final resistance conditions specified by the project.

Other resistances: internal air flow channels, protective nets, air inlet conditions and external system resistance of the unit.

Fan capacity: corresponding air volume under resistance, operating speed and available adjustment range.

Overall machine performance: actual wind speed, uniformity, noise and input power, confirmed according to project requirements.

Aili Industrial has the ability to support fans, motors, control systems and filters, and can jointly confirm the filter parameters and the operating conditions of the FFU machine.

How to install and replace seals

Gasket seal configuration

Check the surface, width and compression conditions of the gasket to ensure continuous sealing contact. The fixed structure of the unit should be pressed evenly around the unit to avoid local gaps.

Tank seal configuration

Check the position and size of the filter tank and FFU blade. Maintain alignment during installation, and implement insertion and positioning conditions according to the matching design.

Replace structure to match

For lower-down FFU, it is necessary to confirm that the filter can be safely removed from the maintenance side; when replacing the structure above, it is necessary to check the upper operating space of the ceiling. The fixing parts, limiting parts and sealing structure should be confirmed together with the replacement method.

The sealing part is responsible for the interface sealing, and the weight of the filter should be borne by the specified support and fixed structure.

Original FFU filter replacement and upgrade

Project status

What needs to be confirmed

Replace with same level

Size, air volume, resistance, sealing and fixed structure

HEPA upgraded to ULPA

Process necessity, fan capacity and complete machine re-verification

U15 upgraded to U16 or U17

Pressure drop, speed adjustment margin and acceptance requirements of designated models

Glass fiber changed to PTFE

Process material requirements, actual pressure drop and component adaptation

Original model discontinued

Original nameplate, drawings, reports and unit operating data

Other brand FFU packages

Installation interface, fan parameters and existing maintenance methods

The same external dimensions are not enough to confirm that they can be directly replaced. After replacement, the air volume, wind speed, sealing and cleaning performance should be checked as required.

Applicable items

Project type

Product supporting requirements

Project type

Product supporting requirements

New clean room

Matched with FFU module and design air volume

local clean area

Configure according to process goals

Clean shed and production line

Selection based on operating parameters of a single unit

Original system upgrade

Check filtration level and fan capacity

Device top FFU

Installation space and interface matching

Filter maintenance and replacement

Confirm replacement parts according to original machine parameters

The specific grade and configuration should be based on process design and acceptance requirements.

Inquiry and customized parameters

Parameter items

Please provide information

FFU information

Brand, model and box structure

filter level

U15, U16, U17 or program requirements

Product size

Frame width, height, thickness and tolerance

Operational requirements

Design air volume or target surface wind speed

resistance conditions

Allowable initial resistance, final resistance and fan parameters

Installation interface

Gaskets, tanks, supports and fixed structures

Replacement method

Upper and lower disassembly or other maintenance methods

Usage environment

Temperature, humidity and process material requirements

Acceptance information

Test items, reports and complete machine verification requirements

Procurement arrangements

Quantity, sample requirements and delivery plan

Post-install verification

After the installation is completed, check the filter peripheral seal, unit air volume and wind speed according to project requirements, and perform corresponding leak detection and clean performance verification.

Keep the initial air volume, wind speed and pressure difference records to facilitate subsequent judgment of the filter status. The FFU group control project should also check the unit address, control settings and operating status to avoid misdiagnosing control differences as filter problems.

Aili industrial supporting support

Aili Industry covers air filter manufacturing, motor manufacturing, independent research and development and production of fans, control system development, sheet metal processing and complete machine assembly.

FFU's matching ULPA filter can be confirmed together with the fan, box and control conditions, providing support for new machine matching, sample verification, original machine replacement and bulk purchasing.

View Aili Industrial FFU products→ Learn about FFU group control system→

Product FAQ

Can FFU's HEPA filter be replaced with ULPA?

Process requirements need to be confirmed first, and then size, sealing, filter resistance and fan capacity need to be checked.

Is the FFU nominal size the filter size?

Not necessarily, the filter installation diagram or actual frame size should prevail.

Do I need to adjust the rotation speed after replacing the ULPA filter?

Confirm based on actual air volume and wind speed, and cannot directly use the original settings to judge performance.

Can the detachable FFU be equipped with a ULPA filter?

The matching package can be evaluated, and the fixed structure, sealing interface and removal space need to be confirmed.

Can it be used with other brands of FFU?

The adaptation conditions can be checked based on the drawings, original filter data and operating parameters.

Do I need to check for leaks again after replacement?

The sealing and related operating performance should be rechecked according to project maintenance and acceptance requirements.

Get FFU filter package plan

Please submit FFU model, filter size, filtration level, target air volume and installation interface information. Aili Industrial will help confirm the ULPA filter configuration based on the unit structure and operating conditions.

Consult FFU filter specifications → Submit original model and drawings →

Confirm the level upgrade conditions → Inquire about replacement parts and batch matching →

Aili Industry - from filters to fans, boxes and controls, provides product support for FFU projects.

Previous article: 
Next article: 
Aili Industrial develops and manufactures FFU, EFU, HEPA/ULPA air filters, high-efficiency air supply vents, fan boxes and other clean air equipment. Relying on motors, fans, control systems, filters and complete machine supporting capabilities, we provide selection and customization support for clean room and production equipment projects.