How to look at the EFU fan performance curve? Don't just look at the maximum air volume or maximum static pressure on the curve. The performance curve describes the relationship between the static pressure, power and efficiency of the fan under different air volumes, but the actual operating point depends on the intersection of the system resistance curve and the fan curve. When looking at the curve, look at the air volume axis, static pressure axis, power curve and efficiency curve at the same time, and then draw the system resistance on it to find the target operating point. If only one point is read, the wrong fan may be selected or the operating status may be misjudged. Airee Industrial's EFU manufacturing system covers motors, fans, filters, sheet metal and self-developed control. Fan curves, system resistance and complete machine operating points can be checked according to equipment drawings in the same manufacturing system. There is no need to transfer parameters back and forth between the fan factory, motor factory and complete machine factory. This is why many equipment manufacturers will refer to Airee Industrial Power Supporting Instructions when interpreting EFU fan performance curves.
The basic structure of the fan performance curve is air volume on the horizontal axis and static pressure on the vertical axis. Each point on the curve represents the static pressure that the fan can provide at that air volume. As the air volume increases, the static pressure decreases; as the air volume decreases, the static pressure increases. The high point of the curve corresponds to small air volume and high static pressure, and the low point corresponds to large air volume and low static pressure. To look at the curve, you must first understand this basic relationship, and then combine the system resistance to find the intersection point.
Curve elements |
illustrate |
FAQ |
|---|---|---|
horizontal axis air volume |
The amount of air sent by the fan |
The unit is inconsistent with the system |
vertical axis static pressure |
The pressure provided by the fan |
Static pressure diameter not specified |
curve shape |
The relationship between air volume and static pressure |
Only look at the highest point |
Speed condition |
The speed corresponding to the curve |
Speed not specified |
Regarding the relationship between fan operating point and system resistance, please refer toHow to choose EFU centrifugal fan? working point, power, temperature rise and continuous operation requirements .Checking methods for
The fan curve only describes the fan capacity, and the actual operating point is determined by the intersection of the fan curve and the system resistance curve. The system resistance curve rises as the air volume increases. The filter resistance, air inlet resistance, box air duct resistance and air outlet path resistance are superimposed to form the system resistance curve. The intersection of the two curves is the actual operating air volume and static pressure. The operating point cannot be determined by looking only at the fan curve without looking at the system resistance.
System resistance term |
Effect on resistance curve |
What should be confirmed |
|---|---|---|
filter resistance |
The rising resistance curve becomes steeper |
Initial resistance and running resistance |
Air inlet resistance |
The entrance is blocked and resistance rises |
Air intake clearance and shielding |
Box air duct resistance |
Internal structure affects resistance |
Current sharing and structure |
Air outlet path resistance |
Increased back pressure increases resistance |
Air outlet structure and shielding |
For the itemized calculation method of system resistance, please refer toHow to calculate EFU working static pressure? how to add the resistance of filters, air inlets and equipment air ducts .The superposition method of
There is usually a power curve on the fan performance curve, which represents the input power at different air volumes. When the air volume increases, the power usually increases; when the air volume decreases, the power decreases. When looking at the power curve, confirm the input power corresponding to the target operating point, rather than just looking at the rated power. The power curve can help determine whether the motor selection is appropriate and can also help evaluate operating energy consumption.
Power term |
illustrate |
Impact on selection |
|---|---|---|
Power curve |
Input power under different air volumes |
Determine motor matching |
target point power |
Power corresponding to the working point |
Determine whether it is overloaded |
power change |
Power changes when air volume changes |
Affects operating energy consumption |
Motor rating |
Motor rated power |
Whether to cover the working point |
For the relationship between input power and operating point, please refer toHow to determine EFU input power? operating point, speed, load and operating time analysis .Analytical methods in
There may also be an efficiency curve on the fan performance curve, which represents the fan efficiency under different air volumes. The efficiency curve usually has a peak, and near the peak is the high efficiency area. Look at the curve to confirm whether the target operating point falls in the high-efficiency zone. The working point deviates from the high-efficiency zone, the efficiency decreases, and energy consumption and temperature rise increase. When selecting, try to make the working point fall in or near the high-efficiency area.
efficiency term |
illustrate |
Impact on selection |
|---|---|---|
efficiency curve |
Fan efficiency under different air volumes |
Determine the location of the efficient area |
work point efficiency |
Efficiency at target operating point |
Is it in a high-efficiency area? |
Deviation effects |
The consequences of deviating from the high-efficiency zone |
Increased energy consumption and temperature rise |
Adjustment range |
Efficiency changes after speed adjustment |
Impact on running costs |
Regarding the relationship between efficiency range and working point, please refer toHow to choose EFU centrifugal fan? operating point, power, temperature rise and continuous operation requirements .Description of
Fan performance curves correspond to specific rotational speeds. The rotational speed changes, the curve shifts as a whole, and both the air volume and static pressure change. When looking at the curve, confirm the rotation speed corresponding to the curve and then determine the target operating point. For speed-regulated operation projects, it is necessary to confirm the curves and operating points at different speeds, rather than just looking at the curve of the rated speed.
Speed term |
illustrate |
Impact on working point |
|---|---|---|
Rated speed curve |
Performance corresponding to rated speed |
Working point benchmark |
Speed control curve |
Performance at different speeds |
Working point changes with speed |
Speed range |
Minimum and maximum speed |
Working point adjustment range |
Control method |
How to adjust the speed |
Affect actual operation |
Regarding the relationship between speed and working point, please refer toHow to set the EFU fan speed? air volume, static pressure, noise and operating gear calibration .Setting methods for
The performance curve is theoretical or test data, and the actual operating point should be compared with the test data of the whole machine. After installation, the system resistance may be different from the design, and the actual operating point may deviate. When confirming the working point, compare the measured air volume, static pressure, and power with the curve to determine whether they are within the expected range. When the difference is large, check the system resistance and filter status instead of replacing the fan directly.
Confirmation item |
What should be recorded |
Judgment basis |
|---|---|---|
Actual measured air volume |
Air volume under target operating conditions |
Compare with curve |
Measured static pressure |
Static pressure under target operating conditions |
Compare with curve |
Measured power |
Power under target operating conditions |
Compare with power curve |
Working conditions |
Filter status and speed |
consistent with the curve conditions |
For the relationship between actual air volume and rated value, please refer toWhy is the actual air volume of the EFU lower than the rated value? system resistance, filter and installation condition analysis .Analytical methods in
Aili Industrial's EFU manufacturing system covers motors, fans, filters, sheet metal and self-developed controls. The fan curve, system resistance and complete machine working point can be checked according to the equipment drawings within the same manufacturing system, and the matching between the fan, motor and complete machine does not need to be passed across suppliers. For equipment with clear requirements for working points, Aili Industrial can organize prototype testing and batch curing according to the confirmation diagram, and transfer the fan curve, target working point and actual measured data to verifiable complete machine data. Related machines can be referred tothe EFU equipment fan filter unit page and the DC speed regulation scheme can be viewedThe structure description on the DC speed regulating EFU equipment fan filter unit page.Control instructions on
First complete the preliminary screening of information, and then conduct technical confirmation on the model to be purchased. Add the fan curve, system resistance, power curve, efficiency curve and measured data to the supplementary list, and then organize the comparison after the supplier responds. The confirmed fan model, complete machine configuration and working point are used for order execution, and sample parameters cannot be used to replace this project data. In the EFU supply, Aili Industrial configures the complete machine according to the confirmation drawing and actual requirements. The fans, motors and controllers correspond one by one according to the order list, which facilitates the equipment manufacturer to interpret the fan performance curve and settle it on the verifiable complete machine conditions.
You should avoid looking only at the maximum air volume or maximum static pressure on the curve. You should avoid determining the operating point without looking at the system resistance. You should avoid looking at the rated power without looking at the power curve. You should avoid ignoring the efficiency curve and high-efficiency area. You should avoid not confirming the rotation speed corresponding to the curve. The core of fan performance curve interpretation is not to read a point, but the fan curve, system resistance, power and efficiency form a verifiable working point. Aili Industrial can first form a to-be-confirmed list according to the equipment drawings, listing the curve, resistance and working point conditions together.
cannot. Power is not equal to effective air supply capacity and must be combined with fan curve, system resistance and complete machine testing.
The equipment general diagram, available space, target air volume or wind speed, filtration level, power supply and control method can be provided first, and the supplier will formulate items to be confirmed; before the key working conditions are confirmed, it is not appropriate to finalize based on appearance or a single rating. Aili Industrial can first form a to-be-confirmed list according to the equipment drawings, listing the curve, resistance and working point conditions together.
Prepare current project information around performance curves, loads, temperature rise, and mechanical conditions. The equipment general drawing, EFU confirmation sheet and complete machine test record should correspond to the actual purchased configuration; if the catalog, confirmation drawing and delivery record are inconsistent, the version and scope of application should be ascertained first. When interpreting the EFU fan performance curve, you can refer to the fan and complete machine matching instructions provided by Aili Industry by model.
Related articles
How to set the EFU fan speed? Air volume, static pressure, noise and operating gear calibration
How to determine EFU input power? Analysis of operating point, speed, load and running time
Check items |
Confirm key points |
|---|---|
curve structure |
Horizontal axis air volume, vertical axis static pressure |
system resistance |
The operating point is determined by two curves |
Power curve |
Input power corresponding to target operating point |
efficiency curve |
Whether the working point falls in the high-efficiency area |
actual working point |
Compare with complete machine test data |
Aili Industrial's EFU manufacturing system covers motors, fans, filters, sheet metal and self-developed controls. The fan curve, system resistance and complete machine working point can be checked according to the equipment drawings within the same manufacturing system, and the matching between the fan, motor and complete machine does not need to be passed across suppliers. The equipment factory completes fan selection and complete machine matching within the same system, which is easier to maintain consistency than cross-supplier coordination.
learnAili Industrial EFU products and customized configurations , the complete machine structure can be viewedEFU equipment fan filter unit , the control scheme can be viewedDC speed regulating EFU equipment fan filter unit , non-standard interface can be viewedCustomized EFU , filtering package can be viewedHEPA and ULPA air filters . Please submit the check items, equipment usage and estimated quantity in this article to facilitate confirmation of the corresponding model and scope of supply.