How to write the EFU power supply voltage into the technical requirements? You cannot just write '220V' or '380V'. The power supply voltage involves rated voltage, allowable fluctuation range, frequency, number of phases, power supply capacity, wiring method, protection configuration and test acceptance method. If only the nominal voltage is written, but not the fluctuation range, the driver may be selected incorrectly; if the frequency and phase number are not written, the on-site power supply may not match; if the test method is not written, it is impossible to confirm whether the voltage is qualified during acceptance. When writing the power supply voltage requirements, the rating, allowable range, wiring, protection and testing must be written clearly together. Ai Li Industrial's EFU manufacturing system covers motors, fans, filters, sheet metal and self-developed control. The power supply voltage, driver matching and wiring methods can be checked according to equipment drawings in the same manufacturing system. There is no need to transmit parameters back and forth between the driver factory, motor factory and complete machine factory. This is why many equipment manufacturers will refer to Ai Li Industrial's electrical solution description when writing EFU power supply voltage requirements.
For power supply voltage requirements, the rated voltage and allowable fluctuation range must first be stated. The on-site power supply of the equipment may fluctuate, and the EFU must work normally within the fluctuation range. Only the nominal voltage is written, not the fluctuation range. The driver may be selected according to the nominal value, and protection or shutdown may occur when the on-site voltage fluctuates. The fluctuation range is generally determined according to equipment power supply conditions and industry practices. When writing technical requirements, the upper and lower limits must be clearly defined.
Voltage term |
What should be stated |
FAQ |
|---|---|---|
Rated voltage |
Equipment power supply nominal voltage |
Only write 220V or 380V |
Fluctuation range |
Allowable voltage upper and lower limits |
The fluctuation range is not written |
frequency |
50Hz, 60Hz or wideband |
Frequency not specified |
Number of phases |
single phase or three phase |
Number of phases not specified |
Ai Li industrialEFU products and customized configurations list electrical parameters and supporting instructions by model. When writing voltage requirements, the equipment manufacturer can directly correspond to the specific model and put the rated voltage, fluctuation range and frequency phase number in the same parameter table.
The power supply voltage requirements must also indicate the power supply capacity and wiring method. The power supply capacity is insufficient and it may trip when starting; the wiring method is unclear and the on-site wiring may be wrongly connected. The power supply capacity is determined based on the EFU rated power and starting current, and the wiring method includes terminal type, wire diameter, and grounding method. These contents are written into the technical requirements, so that on-site power distribution and wiring have a basis.
Power items |
What should be stated |
FAQ |
|---|---|---|
Power capacity |
Circuit breaker and cable capacity |
Insufficient capacity initiates tripping |
Wiring method |
Terminal type, wire diameter, grounding |
The wiring method is not written |
Protect configuration |
Overvoltage, undervoltage, overcurrent protection |
Protection configuration is not agreed upon |
Starting current |
Start peak and protection matching |
Starting current is not specified |
For the matching method of driver and power supply, please refer toHow does the EFU DC motor match the EFU? Air volume static pressure, control and complete machine testing methods andHow to match EC motor for EFU? The instructions in the operating point, speed regulation, power and control interface base the power supply capacity and wiring requirements on the electrical conditions of the complete machine.
The power supply voltage requirements also need to be implemented in the driver selection. The input voltage range of the driver must cover the fluctuation range of the on-site voltage, and the driver cannot be selected based on the nominal voltage alone. If the voltage fluctuation exceeds the range of the driver, the driver may be damaged or damaged; if the voltage is low, the driver may not start or the output may be insufficient. When writing technical requirements, the driver input range should be matched with the on-site voltage conditions.
drive item |
What should be stated |
Impact on power supply requirements |
|---|---|---|
input range |
Driver allowed voltage range |
Whether to cover on-site fluctuations |
frequency range |
frequency allowed by the drive |
Whether it matches the on-site power supply |
protection function |
Overvoltage, undervoltage, overcurrent protection |
Protect equipment during abnormal times |
Output capability |
Output power matches the motor |
Whether the motor can operate normally |
For driver configuration under special power conditions, please refer toHow to customize special power supply EFU? input conditions, drivers, protection and interface validation .Check methods for
The power supply voltage requirements must be matched with test methods. The conditions under which the test is performed, where the test points are, what instruments are used, and what the judgment criteria are are all clearly stated. Only the voltage requirements are written, and the test methods are not written. Qualification cannot be confirmed during acceptance. The test method must be reproducible. If different people measure using the same method, the results should be consistent.
Test items |
What should be stated |
FAQ |
|---|---|---|
Test conditions |
Input voltage and load status |
Conditions not agreed upon |
Measuring point location |
Power terminal or driver input |
Measuring point not specified |
Instrument requirements |
Multimeter or voltage recorder |
Instrument not agreed |
Judgment criteria |
Allowable deviation range |
The standard is not written |
Regarding the relationship between electrical testing and acceptance, please refer toHow to troubleshoot if EFU cannot start? the power supply, control signal, motor and protection status .How to check
For acceptance of the power supply voltage, the voltage, startup and protection must be confirmed together. The power supply voltage is qualified only if the voltage is within the allowable range, the startup is normal, and the protection function is effective. If all three are confirmed, the power supply voltage is qualified. Only confirm the voltage value without confirming startup and protection. Problems may occur during on-site operation.
Acceptance items |
What should be confirmed |
Judgment basis |
|---|---|---|
voltage range |
The measured voltage is within the allowable range |
Compare with technical requirements |
Start testing |
Starting current and protection action |
Compare with design value |
protection function |
Overvoltage, undervoltage, overcurrent protection |
Compare with protection settings |
record retention |
Test data and conditions |
test record |
In the EFU project, Aili Industry organizes electrical acceptance according to the equipment drawings and agreed conditions, files the voltage, starting and protection data together with the confirmation diagram, and then solidifies the batch configuration. Equipment factory can directly compareThe complete machine description on the EFU equipment fan filter unit page matches the acceptance record with the factory data.
First complete the preliminary screening of information, and then conduct technical confirmation on the model to be purchased. Add the rated voltage, fluctuation range, frequency phase number, power capacity, drive range and test method to the supplementary list, and then organize the comparison after the supplier responds. The confirmed electrical parameters, complete machine configuration and wiring methods are used for order execution, and sample parameters cannot be used to replace the data of this project. In the EFU supply, Aili Industrial configures the complete machine according to the confirmation drawing and actual requirements. The driver, motor and controller correspond one by one according to the order list, which facilitates the equipment manufacturer to adjust the power supply voltage requirements to the verifiable complete machine conditions.
It should be avoided to only write the nominal voltage but not the fluctuation range, to avoid not writing the frequency and phase number, to avoid not selecting the driver according to the on-site voltage, to avoid not writing the power supply capacity and wiring method, and to avoid only confirming the voltage value without confirming startup and protection. The core of the supply voltage requirements is not to write a number, but the rating, fluctuation range, driver matching, wiring and test acceptance to form a verifiable closed loop. Aili Industrial can first form a to-be-confirmed list according to the equipment drawings, listing the voltage, capacity and test conditions together.
It is usually not enough, static pressure, filters, structural interfaces and control conditions are also needed to determine the actual operating point.
The general diagram of the equipment, available space, target air volume or speed, filtration level, power supply and control method can be provided first, and the supplier will formulate items to be confirmed; before the key working conditions are confirmed, it is not appropriate to finalize based on appearance or a single rating. Aili Industrial can first form a to-be-confirmed list according to the equipment drawings, listing the voltage, capacity and test conditions together.
Prepare current project information around functional boundaries, rated operating conditions and equipment interfaces. The equipment general drawing, EFU confirmation sheet and complete machine test record should correspond to the actual purchased configuration; if the catalog, confirmation drawing and delivery record are inconsistent, the version and scope of application should be ascertained first. When writing the EFU power supply voltage requirements, you can refer to the electrical and complete machine supporting instructions provided by Aili Industry by model.
Related articles
Check items |
Confirm key points |
|---|---|
Rated voltage |
Nominal voltage and allowable fluctuation range |
Frequency phase number |
50Hz/60Hz, single phase/three phase |
Power capacity |
Circuit breaker and cable capacity |
Drive range |
Input range covers field fluctuations |
Test acceptance |
Voltage, start-up and protection are confirmed together |
Aili Industrial's EFU manufacturing system covers motors, fans, filters, sheet metal and self-developed controls. Supply voltage, driver matching and wiring methods can be checked according to equipment drawings within the same manufacturing system, and the matching between drivers, motors and complete machines does not need to be passed across suppliers. The equipment factory completes the matching of power supply voltage requirements and complete machines within the same system, which is easier to maintain consistency than cross-supplier coordination.
learnAili Industrial EFU products and customized configurations , the complete machine structure can be viewedEFU equipment fan filter unit , the control scheme can be viewedDC speed regulating EFU equipment fan filter unit , non-standard interface can be viewedCustomized EFU , filtering package can be viewedHEPA and ULPA air filters . Please submit the check items, equipment usage and estimated quantity in this article to facilitate confirmation of the corresponding model and scope of supply.