How does the EFU DC motor match the EFU? Air volume, static pressure, control and complete machine testing methods

How to match EFU DC motor to EFU? You cannot just look at the voltage and power on the motor nameplate. When the DC motor is installed into the EFU, it must form an operating point together with the fan curve, filter resistance and the internal air duct of the equipment. If the motor power is selected to be small, the operating point deviates from the high-efficiency zone, and the temperature rise rises; if the motor power is selected to be high, the efficiency range does not match, and energy consumption is wasted. The core of matching is to put the target air volume, static pressure, motor rated parameters, speed regulation method and complete machine test data in the same table for verification. Ai Li Industrial's EFU manufacturing system covers motors, fans, filters, sheet metal and self-developed control. The working points of DC motors, fans and complete machines can be checked according to equipment drawings in the same manufacturing system. There is no need to transfer parameters back and forth between motor factories, fan factories and complete machine factories. This is why many equipment manufacturers will refer to Ai Li Industrial Power Supporting Instructions when matching EFU DC motors.

Working point matching: the motor should follow the fan curve

The working point of the DC motor is determined by the fan curve and the system resistance curve. When selecting a motor, first look at the shaft power corresponding to the target air volume and static pressure, and then check whether the rated power of the motor covers this operating point and leaves a margin. Selecting a motor only based on the maximum power of the fan may cause the motor to run in a low load area for a long time, resulting in low efficiency; selecting only based on the rated air volume will increase the resistance after dust accumulation in the filter, and the motor may be overloaded. When matching, the working point under initial resistance conditions and operating resistance conditions should be looked at at the same time.

match

What should be confirmed

FAQ

target operating point

Shaft power at target air volume and static pressure

Only give rated air volume

Motor rated power

Whether to cover the working point and leave a margin

Insufficient or excessive margin

Initial resistance and running resistance

Operating point under two conditions

Only counting the initial resistance

efficiency range

Whether the working point falls in the high-efficiency area

Only look at the rated power

Regarding the relationship between fan operating point and system resistance, please refer toHow to choose EFU centrifugal fan? The checking method of working point, power, temperature rise and continuous operation requirements establishes the motor power matching based on the working point of the whole machine. For projects that require a complete DC speed regulation solution, please refer tofan filter unit page of DC speed regulating EFU equipment .Complete machine and control instructions on the

Electrical matching: power supply, starting and protection must correspond

Electrical matching of DC motors, including supply voltage, starting current, protection configuration and speed control interface. The power supply voltage must be consistent with the equipment power supply; the starting current must consider the power supply capacity and protection settings; the protection configuration must cover overcurrent, overtemperature, and blocked rotor; the speed adjustment interface must match the equipment control method. If the electrical matching is incorrect, the motor may fail to start, have frequent protection or speed regulation failure.

Electrical items

What should be confirmed

FAQ

Supply voltage

Is it consistent with the device power supply?

voltage mismatch

Starting current

Starting peak value and power capacity

Trip on startup

Protect configuration

Overcurrent, overtemperature, stall protection

Lack of protection or malfunction

Speed ​​control interface

0-10V, PWM or communication

The interface is not compatible with the device

Ai Li industrialEFU products and customized configurations list motor and driver matching instructions by model. When checking electrical matching, the equipment manufacturer can directly correspond to the specific model and put power supply, starting and protection conditions in the same electrical confirmation form.

Speed ​​matching: DC motor speed range and mapping

One of the advantages of DC motors is their wide speed range. When matching, it is necessary to confirm whether the speed adjustment range covers the equipment operating gear, and whether there are actual measured data for the speed, air volume, power and noise at each gear. The mapping relationship between the control command and the rotational speed must be calibrated by actual measurement. It cannot be assumed that 50% of the command means 50% of the air volume. The speed adjustment range is narrow, and the equipment may be unstable when running at low gears; the mapping is inaccurate, and the air volume deviation at each gear is large.

Speed ​​control item

What should be confirmed

Impact on matching

Speed ​​range

Minimum and maximum speed

Whether to cover the device gear

Instruction mapping

Correspondence between command, rotation speed and air volume

Is the gear air volume accurate?

Power of each gear

Input power of each gear

Determine motor load

Low speed stability

Is it stable at low speed?

Is low-speed operation reliable?

For detailed methods involving speed adjustment settings, please refer toHow to set EFU multi-speed speed adjustment? The gear division and parameter calibration in equipment linkage, abnormal status and acceptance points correspond to the DC motor speed regulation and the equipment operation stage.

Temperature rise and heat dissipation: continuous operation must be confirmed separately

The DC motor runs continuously inside the EFU, and the temperature rise is the key point for matching. Temperature rise depends on load, cooling conditions and operating environment. The operating point deviates from the high-efficiency area, the loss increases, and the temperature rise rises; the EFU box's heat dissipation conditions are poor, and the temperature rise is higher. When matching, confirm the temperature rise record under the target working conditions and whether the box has sufficient heat dissipation conditions. Ultra-thin or compact models have tighter space and worse heat dissipation conditions and need to be checked separately.

Temperature rise term

What should be confirmed

FAQ

Continuous operation temperature rise

Temperature rise record under target operating conditions

Only give short-term data

Heat dissipation conditions

Box heat dissipation area and ventilation

The box is closed and has no heat dissipation

protection logic

Overtemperature slowdown or shutdown

No temperature protection

ambient temperature

Device internal ambient temperature

Ambient temperature is not considered

In the EFU project, Aili Industrial checked the temperature rise of the DC motor and driver according to continuous operating conditions, and confirmed the heat dissipation conditions as part of the complete machine configuration. For heat dissipation check methods of ultra-thin models, please refer toHow to choose ultra-thin EFU? Space, Air Volume Static Pressure, Heat Dissipation and Maintenance Points .Instructions in

Mechanical matching: speed, vibration and fixation

Mechanical matching of DC motors, including speed range, vibration state and fixation method. The motor speed must match the fan impeller. Excessive speed may cause vibration and noise; the motor must be firmly fixed and vibration reduction measures must be in place to prevent vibration from being transmitted to the equipment structure. When matching, check the connection method, dynamic balance status and fixed points of the motor and fan.

Mechanical items

What should be confirmed

FAQ

Speed ​​matching

Motor speed and fan impeller

Too high rotation speed and large vibration

Connection method

Direct-coupled or belt drive

connect discord

Fixed method

Motor and box fixed

Insufficient fixed points

vibration state

Operational Vibration and Dynamic Balance

Vibration is transmitted to the device

Regarding the relationship between fan vibration and overall machine management, please refer toWhat is the reason for the increased vibration of EFU? The troubleshooting ideas in how to judge the impeller, motor, fixed structure and resonance are to check the mechanical status of the motor and the fixed conditions of the whole machine.

Whole machine test: matching results must be verified with data

The matching of DC motor and EFU must ultimately be verified with complete machine test data. The test should cover the target air volume and static pressure, speed and power of each gear, continuous operating temperature rise, vibration and noise. It only measures the highest gear and cannot judge whether the middle gear is stable; it only measures short-term data and cannot judge the continuous operating status. The test data should be compared with the motor rated parameters, fan curve and confirmation chart. If the difference is large, check the matching conditions instead of directly replacing the motor.

Test items

What should be recorded

Judgment basis

Target operating conditions

Air volume, static pressure, power

Compare with design value

Each gear

Speed, air volume, power, noise

Compare with calibration table

Continuous operation

Temperature rise curve and stability

Whether the limit is exceeded

Vibration and Noise

Vibration and noise at each gear

Does it affect the equipment?

In the EFU project, Aili Industry organized the complete machine test according to the equipment drawings and agreed working conditions, and verified the DC motor, fan and complete machine data together. The equipment factory completes the matching of motors and complete machines within the same manufacturing system, which makes it easier to maintain data consistency than cross-supplier coordination. Related machines can be referred tothe EFU equipment fan filter unit page.Structural description on

Aili Industrial EFU DC motor matching

Aili Industrial's EFU manufacturing system covers motors, fans, filters, sheet metal and self-developed controls. DC motor selection, speed mapping and complete machine testing can be completed within the same manufacturing system, and the matching between motors, fans and complete machines does not need to be passed across suppliers. For projects that require DC speed regulation or equipment linkage, Aili Industrial can organize confirmation drawings, prototype verification and batch solidification according to equipment drawings, and put the working point, speed regulation range, temperature rise and test data into verifiable complete machine data.

How to form executable confirmation results

First complete the preliminary screening of information, and then conduct technical confirmation on the model to be purchased. Add the working point, electrical parameters, speed range, temperature rise and complete machine test requirements to the supplementary list, and then organize the comparison after the supplier responds. The confirmed motor model, complete machine configuration and control interface are used for order execution, and sample parameters cannot be used to replace this project data. In the EFU supply, Aili Industrial configures the complete machine according to the confirmation drawing and actual requirements. The motor, fan and control correspond one by one according to the order list, which facilitates the equipment factory to match the DC motor to the verifiable complete machine conditions.

Misunderstandings to avoid

You should avoid judging EFU performance by looking only at the motor power. Power is not equal to the effective air supply capacity. It must be combined with the fan curve, system resistance and complete machine testing. It should be avoided to only select the motor based on the rated air volume and ignore the operating resistance. It should be avoided to default the control command equal to the air volume ratio. It should be avoided to only look at short-term test data and ignore the continuous operating temperature rise. It should be avoided to only measure the highest gear and ignore the stability of the middle gear. The core of DC motor matching is not how good the parameters of the motor itself are, but whether the motor, fan, filter, box and control form a verifiable working point. Aili Industrial can first form a to-be-confirmed list according to the equipment drawings, listing the working points, electrical and test conditions together.

Related questions and answers

Can EFU performance be judged by just looking at the motor power?

cannot. Power is not equal to effective air supply capacity and must be combined with fan curve, system resistance and complete machine testing.

How to promote EFU DC motor matching when the project information is incomplete?

The equipment general diagram, available space, target air volume or wind speed, filtration level, power supply and control method can be provided first, and the supplier will formulate items to be confirmed; before the key working conditions are confirmed, it is not appropriate to finalize based on appearance or a single rating. Aili Industrial can first form a to-be-confirmed list according to the equipment drawings, listing the working points, electrical and test conditions together.

What specific information do I need to prepare for this question?

Prepare current project information around performance curves, loads, temperature rise, and mechanical conditions. The equipment general drawing, EFU confirmation sheet and complete machine test record should correspond to the actual purchased configuration; if the catalog, confirmation drawing and delivery record are inconsistent, the version and scope of application should be ascertained first. When matching EFU DC motors, you can refer to the instructions for matching the motor and complete machine provided by Aili Industry by model.

Related articles

How to choose EFU centrifugal fan? Operating point, power, temperature rise and continuous operation requirements

How to match EC motor for EFU? Working point, speed regulation, power and control interface

How to choose EFU AC motor? Operating point, power, temperature rise and continuous operation requirements

Key points for selection and acceptance inspection

Check items

Confirm key points

Working point matching

The motor power covers the target operating point and leaves a margin

Electrical matching

Power supply, startup, protection, speed adjustment interface

Speed ​​matching

Measured calibration of speed range and command mapping

Temperature rise and heat dissipation

Continuous operation temperature rise and heat dissipation conditions

Whole machine test

Various gears, continuous operation, vibration and noise verification

Aili Industrial EFU selection and procurement support

Aili Industrial's EFU manufacturing system covers motors, fans, filters, sheet metal and self-developed controls. DC motor selection, speed mapping and complete machine testing can be completed within the same manufacturing system, and the matching between motors, fans and complete machines does not need to be passed across suppliers. The equipment factory completes the matching of DC motors and complete machines within the same system, which makes it easier to maintain data consistency than cross-supplier coordination.

learnAili Industrial EFU products and customized configurations , DC speed regulation solutions can be viewedDC speed regulating EFU equipment fan filter unit , the structure of the whole machine can be viewedEFU equipment fan filter unit , filter package can be viewedHEPA and ULPA air filters . Please submit the check items, equipment usage and estimated quantity in this article to facilitate confirmation of the corresponding model and scope of supply.

Aili Industrial develops and manufactures FFU, EFU, HEPA/ULPA air filters, high-efficiency air supply vents, fan boxes and other clean air equipment. Relying on motors, fans, control systems, filters and complete machine supporting capabilities, we provide selection and customization support for clean room and production equipment projects.

product

Quick links

Join a global perspective

Get the latest industry white papers and technology updates.
© Suzhou Aili Industrial Co., Ltd. All rights reserved.