Direct answer: To achieve 0-10V speed regulation by EFU, three levels need to be confirmed: signal wiring, that is, the analog input terminal and the common terminal; control mode, that is, switching the EFU control card to 0-10V analog mode; speed calibration, that is, confirming the rotation speed or wind speed corresponding to 0V and 10V, and the status when the signal is lost. After the wiring is completed, adjust the fan speed through the external 0-10V signal or the device PLC analog output; during calibration, you need to confirm the corresponding relationship between voltage and speed, and set the safe state when the signal is abnormal.
0-10V speed regulation is a common control method when the EFU is linked to the equipment PLC or host system. The following will start from four aspects: signal wiring, control mode, speed calibration and abnormal status.
EFU's 0-10V analog control usually involves the following terminal blocks:
terminal |
Function |
illustrate |
|---|---|---|
0-10VIN |
Analog input |
Receive external 0-10V control signal |
COM/GND |
Public end |
Analog signal reference ground |
+10V OUT |
Internal reference voltage output |
Available on some models, an external potentiometer can be connected to achieve manual speed adjustment. |
Tacho / FG |
Speed feedback signal |
Some models provide speed pulse or voltage feedback |
Some control cards use 2-pin terminals for analog control and provide DC millivolt signal output to read speed and motor torque percentage. For EC fans, common wiring includes: one wire for fixed 10VDC output, one wire for 0-10VDC input, one wire for ground, and one wire for speed signal.
Please note when wiring:
It is recommended to use shielded wires for analog signal lines, and the shielding layer should be grounded at one end;
Signal lines and power lines are routed separately to reduce interference;
Confirm the range and polarity requirements of the analog input of the EFU control card.
Most EFU control cards support multiple control modes, 0-10V analog control is only one of them. Common patterns include:
Local manual control: adjust the speed through the potentiometer on the board;
Analog remote control: adjusted through external 0-10V signal;
Network control: controlled through communication protocols such as RS485 and Modbus.
Control mode is usually selected via DIP switches or parameter settings. Some control cards provide three options: network speed control, manual speed control and analog speed control. After switching modes, you usually need to power off and restart to take effect.
For Aili Industrial EFU, the control method can be configured as potentiometer, 0-10V, Modbus or wireless monitoring and other solutions according to the equipment requirements. Some products support stepless adjustment of wind speed and can be controlled through 0-10V signals. Related products can be referencedEquipment-side fan filter unit (EFU) and70mm ultra-thin EFU。
The core of 0-10V speed regulation is to confirm the corresponding relationship between the voltage signal and the fan speed or face wind speed. The recommended calibration steps are as follows:
Step 1: Confirm the control scope
Determine the EFU's minimum and maximum operating rpm or wind speed. Some control cards support setting the minimum set point, which can limit the minimum speed range corresponding to the 0-10V signal.
Step 2: Measure the correspondence
Input 0V signal to record whether the fan stops or maintains the minimum speed;
Input 10V signal and record whether the fan reaches the maximum speed;
Measure separately at the midpoint to confirm whether the correspondence is smooth.
Step 3: Confirm the correspondence between signal and speed
For EC fans, the 0-10V signal usually corresponds to a certain range of modulation levels or speed ranges. The actual correspondence must be based on the technical documentation of the EFU control card.
Step 4: Record calibration data
Record the corresponding relationship between voltage and speed in the equipment debugging file to facilitate subsequent maintenance and fault diagnosis.
The abnormal status setting of 0-10V speed regulation mainly involves signal abnormality and fan abnormality.
abnormal situation |
Suggested handling |
|---|---|
Signal line broken |
Set to stop, minimum speed or maintain previous state |
Signal out of range |
Run at maximum speed or trigger alarm |
Signal fluctuation or interference |
Add filtering or use shielded wire |
No signal input |
Set default status according to project requirements |
Some EFU control cards are in analog mode, and the operating status and set values are determined by analog signals, so it is necessary to confirm the safe behavior when there is no signal.
Abnormal speed feedback: If the EFU provides a speed feedback signal, you can determine whether the fan is operating normally by comparing the set speed and feedback speed;
Abnormal current: Some control cards can monitor the motor current to determine whether it is overloaded or blocked;
Communication anomalies: Even if 0-10V analog control is used, some control cards can still respond to communications, enabling status monitoring and abnormal reporting.
Universal controllers usually provide a variety of alarm modes, including input high and low limit alarms, feedback or output alarms, analog feedback alarms, etc. The appropriate alarm mode can be selected according to project requirements, and the output behavior when abnormality is determined through the alarm or interlock mode.
It is recommended to provide: when communicating with the project:
EFU model and control card specifications;
Analog output specifications of the equipment PLC or control system;
Target wind speed range and corresponding voltage;
Signal line length and wiring environment;
Whether a speed feedback signal is needed;
The expected state when the signal is abnormal;
Whether local manual control needs to be retained at the same time;
Whether it needs to coexist with the communication method.
The control system of Aili Industrial EFU is independently developed and the control method can be configured according to the equipment requirements. For 0-10V speed regulation requirements, the EC or DC fan solution can be combined to achieve stepless speed regulation and be connected to the equipment PLC or upper-level system. More products are available for referenceCustom EFU andDC EFU equipment fan filter unit。
Usually connected to the analog input terminal and common terminal on the control card. The specific terminal definitions are subject to the EFU control card manual.
uncertain. 0V may correspond to stop, minimum speed or maintain the previous state, depending on the settings of the control card, which needs to be confirmed during debugging.
Usually corresponds to the maximum rotation speed or a certain range of modulation levels, which is actually subject to the control card specifications.
The analog control mode is usually selected through DIP switches or parameter settings. After switching, it needs to be powered off and restarted to take effect.
It is recommended to use shielded wires and run them separately from power wires to reduce signal interference.
Some models provide speed feedback signal output, which can read speed or pulse signals. Please confirm whether the control card supports it.
Depends on exception status settings. It is recommended to confirm the behavior when there is no signal during debugging and set it according to the device safety requirements.
Some control cards support simultaneous response communication for analog control and can realize status monitoring. Please confirm the specifications of the control card.