The FFU seems to be a relatively compact clean air device, but when you take it apart, you will find that it is actually an air filtration system with multiple core components working together.
A common FFU mainly includes:
Cabinet | Motor | Fan | HEPA/ULPA filter | Control system | Air inlet structure | Air outlet structure | Electrical components
These components are not simply installed in a box.
The real design logic of FFU is:
Target air volume and wind speed → Determine the air treatment needs → The filter generates resistance → The fan provides the corresponding air volume and pressure → The motor drives the fan → The control system manages the operating status → The box forms a reasonable air duct → The whole machine outputs filtered air
Therefore, the key to understanding the FFU structure is not only to know 'what's inside', but more importantly, to understand why these components need to match each other.。
First, let’s quickly understand the basic composition of FFU through a table.
FFU composition |
Main function |
FFU composition |
Main function |
|---|---|---|---|
cabinet |
Carrying components and forming air ducts |
motor |
Drive fan operation |
fan |
Provide air volume and pressure |
HEPA/ULPA |
Filter air particles |
control system |
Start/stop, speed adjustment, management |
Air inlet structure |
guide air in |
Air outlet structure |
Output filtered air |
Electrical components |
Power supply, communication, control |
The specific internal structure of FFU with different sizes, different air volumes and different application scenarios will be different.
For example, ordinary clean room FFU and ultra-thin FFU/EFU installed inside semiconductor equipment may have completely different requirements for cabinet height, fan size, filter structure and electrical layout.
no.
The box looks like just the outermost metal structure of the FFU, but it also plays the role of structural support and internal air organization .
The FFU cabinet mainly needs to be completed:
Fixing fans and motors | Installing filters | Arranging control and electrical components | Forming internal air channels | Installing with clean rooms or equipment
Therefore, the cabinet design will be directly affected by the installation space.
Conventional clean room FFU usually needs to focus on confirming the length, width and ceiling installation method.
Device-side applications often also focus on:
Overall height | Air inlet position | Air outlet direction | Fan layout | Electrical interface location | Maintenance space
Especially in semiconductor equipment, EFEM, SMT equipment and automation equipment, the installation space may be relatively compact. In this case, the FFU box structure needs to match the equipment itself.
The fan is one of the core components in the FFU aerodynamic system.
After FFU is running, the fan needs to keep the air flowing and overcome the air resistance generated by the filter and the system.
It can be simply understood as:
The fan rotates → air enters the FFU → air volume and pressure are established → air overcomes filter resistance → filtered air is sent out from the air outlet surface
Therefore, FFU fan selection cannot only look at the 'maximum air volume'.
Also need to consider:
Fan parameters |
Main content |
Fan parameters |
Main content |
|---|---|---|---|
Air volume |
actual air handling capacity |
wind pressure |
Ability to overcome system resistance |
Speed |
Affect operating point |
power |
Input power situation |
efficiency |
Operating performance under different working conditions |
noise |
Usage environment requirements |
speed regulation |
Do you need to change the running status? |
working point |
Match system resistance |
Pay special attention to:
The maximum air volume tested by the fan alone is not equal to the actual air volume of the FFU complete machine after the filter is installed.
What should really be concerned about is the operating status of the fan under actual resistance conditions after it is installed in the FFU.
The motor is responsible for driving the fan impeller to rotate.
Therefore, the motor and fan actually form the power system of the FFU.
The basic relationship can be expressed as:
The motor inputs electric energy → drives the fan impeller → establishes air flow → overcomes the resistance of the filter and system → outputs the target air volume
FFU can adopt different motor and drive solutions according to product and project requirements, such as AC, DC, EC, etc.
The different options are:
Control method | Speed regulation capability | Input power | Operating characteristics | System cost
There may be differences in other aspects.
Therefore, when choosing FFU, it is not recommended to simply judge 'which motor is better', but to match it according to the actual operation requirements of the project.
Because what FFU really needs is a power system that meets the working conditions of the entire machine.
For example, a project requires:
Specific size + designated air volume + designated air speed + H14 filter + certain system resistance
At this time, the fan and motor need to be matched around this operating point.
If you only choose a fan with a large air volume, you do not consider:
Filter resistance | Air duct structure | Fan efficiency | Motor power | Speed regulation method
The final operating status of the complete machine may not meet the project requirements.
Therefore, a more reasonable design idea for the FFU power system is:
Project requirements → Determine operating conditions → Match fans → Match motors → Complete machine verification
The fan solves 'how the air flows', and the filter solves 'how the air filters'.
FFU can often be configured with HEPA or ULPA filters depending on project requirements.
filter |
Common grades |
Main function |
Selection attention |
|---|---|---|---|
HEPA |
H13,H14 |
High efficiency particle filtration |
Efficiency, air volume, resistance |
ULPA |
U15,U16,U17 |
Higher level particle filtration |
Efficiency, resistance, application requirements |
Filter selection should not just look at the efficiency level.
Also need attention:
Filtration efficiency | Rated air volume | Initial resistance | Size | Filter material | Structure | Sealing method | Usage environment
Because the filter itself is also one of the sources of resistance in the FFU air system.
This is a very critical point in understanding the FFU structure.
Air creates resistance as it passes through the filter.
The fan needs to overcome this resistance to maintain the required air flow.
therefore:
Filter resistance changes → System resistance changes → Fan operating point changes → FFU actual air volume may change
This is why you cannot simply replace the H14 filter with filters of other structures or levels, and then think that other parameters of FFU do not need to be adjusted at all.
If the filter resistance changes significantly, it is necessary to re-confirm the operating status of the fan and the entire machine.
For a single FFU, the control system can be responsible for basic start, stop and speed adjustment.
But when there are dozens or hundreds of FFUs in the project, the importance of the control system will increase significantly.
Depending on the project configuration, the FFU control system can achieve:
Start and stop control | Speed adjustment | Partition management | Working mode | Duty mode | Single machine management | Running status view
For example, a clean room may have different requirements for FFU operating status during normal production and non-production periods.
At this time, the equipment operation mode can be adjusted according to the project design without the need to go to the site one by one.
Usually not exactly the same.
Small projects with a small number can use relatively simple control methods.
Aili Industrial can configure corresponding controllers according to small FFU/EFU projects. For example, the 86-type controller can be used to control up to 32 devices, and can perform area, wind speed, start-stop and status management according to the configuration.
When the number of FFU further increases, computer group control can be considered based on the project.
Computer group control can be carried out according to the system design:
Partition setting|Working speed setting|Duty speed setting|Start and stop management|Single machine control|Running status management
This is more suitable for a large number of FFU systems.
The air inlet structure is responsible for introducing air into the FFU.
While it may seem like a simple structure, it affects how the internal air enters the fan.
When designing, you usually need to consider:
Air inlet space | Fan location | Installation environment | Equipment height | Maintenance methods
For conventional clean room FFU, the installation space is usually relatively sufficient.
The space of FFU/EFU on the equipment side may be relatively compact, so the air inlet method, fan layout and overall height need to be considered together.
This is why the equipment-side FFU cannot simply be reduced in size according to the ordinary clean room FFU.
FFU ultimately needs to send filtered air into the clean area.
Therefore, in addition to 'how much air volume', the distribution of air when it comes out of the air outlet surface is also worthy of attention.
Especially in semiconductor equipment, precision manufacturing and some high-cleaning applications, there may be higher requirements for the uniformity of wind speed on the air outlet surface.
Factors affecting the air outlet status include:
Fan structure | Fan position | Air duct inside the box | Filter structure | Air outlet area | Actual operating air volume
Therefore, FFU cannot only pursue a larger total air volume.
In some applications, wind speed uniformity and airflow stability are also important design parameters.
Because the parameters of a single component are qualified, they cannot directly represent the operating status of the entire FFU machine.
For example:
The fan has its own performance curve | The filter has its own resistance | The box will affect the air flow | The control system will change the fan speed
After these parts are assembled together, the real FFU working state is formed.
Therefore, the FFU complete machine needs to pay attention to:
Test direction |
main purpose |
Test direction |
main purpose |
|---|---|---|---|
Air volume |
Confirm air handling capacity |
wind speed |
Confirm the air outlet status |
power |
Confirm input |
noise |
Assess operating environment |
Running status |
Check equipment operation |
Control function |
Check speed regulation and control |
Filter related |
Confirm project requirements |
Whole machine matching |
Verify component collaboration |
During the manufacturing process of fans and FFU products, Aili Industries will conduct corresponding testing around core components, assembly processes and complete machine operation.
For FFU, the fan, motor, control system, filter and box are not independent of each other.
If one parameter changes, other components may need to be adjusted accordingly.
Aili Industry has established a product system from core components to complete machines around FFU, EFU and clean air equipment, covering:
Motor→Fan→Control system→HEPA/ULPA filter→Sheet metal→Complete machine assembly and testing
The value of this model is mainly reflected in the project matching ability.
For example:
Project changes |
Need to consider collaboratively |
Project changes |
Need to consider collaboratively |
|---|---|---|---|
Increased air volume |
Fans, filters |
height reduction |
Fan, box, filter |
Filter level changes |
Resistance, fan |
Increased wind speed |
Fan, air pressure, filter |
Group control required |
Motor, control system |
Non-standard size |
Sheet metal, fans, filters |
special environment |
Material, structure |
Device side application |
height, interface, maintenance |
In this way, when facing standard FFU, ultra-thin FFU/EFU, device-side applications, and non-standard projects, components can be matched based on the needs of the entire machine.
no the same.
Application scenarios |
focus on |
Application scenarios |
focus on |
|---|---|---|---|
clean room |
Air volume, filtering, group control |
Semiconductor equipment |
Height, uniformity, cleanliness |
EFEM |
Size, equipment adaptation |
SMT equipment |
Installation space, maintenance |
Lithium battery |
Air volume, wind speed, environment |
photovoltaic |
Cleanliness, system configuration |
precision optics |
Particle control, stability |
Biomedicine |
Filtration and cleaning requirements |
Therefore, even if it is called FFU, the internal configuration and structure in different applications may not be exactly the same.
In addition to dimensions and price, it is recommended to confirm at least the following.
Need confirmation |
Main parameters |
Need confirmation |
Main parameters |
|---|---|---|---|
fan |
Air volume, wind pressure, speed |
motor |
Type, power, speed regulation |
filter |
Level, resistance, size |
cabinet |
Material, size, structure |
control |
Single machine, centralized, group control |
power supply |
Voltage and electrical requirements |
The whole machine |
Air volume, wind speed, power |
Install |
Ceiling or equipment side |
If it is a non-standard equipment project, it is also recommended to provide equipment installation space and target operating conditions.
If you select from the perspective of the internal structure of FFU, you can understand it in the following order:
Project application → Installation space → Target air volume and wind speed → Filtration level → Filter resistance → Fan air volume and air pressure → Motor and driving mode → Control mode → Box structure → Complete machine test confirmation
The FFU that is truly suitable for the project is not that one component parameter is particularly outstanding, but that the core components are reasonably matched around the actual working conditions.
Aili Industrial develops and manufactures products around motors, fans, control systems, HEPA/ULPA filters, sheet metal and FFU/EFU complete machines. It can configure corresponding products according to clean rooms, semiconductor equipment, electronic manufacturing, lithium batteries, photovoltaics and other clean air projects.
FFU usually includes a box, motor, fan, HEPA or ULPA filter, control system, air inlet and outlet structure, and electrical components.
Different components perform different functions. The fan is responsible for providing air power, the filter is responsible for filtering particulate matter, the motor is responsible for driving, and the control system is responsible for operation management. Therefore, what is more important is the overall matching of each component.
no. The fan needs to be matched according to the target air volume, air pressure, filter resistance, installation space and operating requirements.
It is not recommended to only change the filtering level and ignore other parameters. Changes in filter grade and structure may be accompanied by changes in resistance, and the operating status of the FFU machine needs to be re-confirmed.
The control system is used for equipment start and stop, speed regulation and operation management. A large number of FFU projects can also be partitioned and centrally managed through group control.
It can be matched according to the equipment installation space, fans, filters and structural requirements, but the overall height needs to take into account the air volume, resistance and internal component layout.
Because the fan, filter, box and control system will jointly determine the actual operating status after assembly, individual component parameters cannot fully represent the performance of the entire machine.
FFU fan filter unit | HEPA/ULPA high efficiency filter | FFU group control system
What is FFU? Structure, working principle, application scenarios and selection guide