Number of views: 5151 Author: Aili Industry Release time: 2026-10-04 Source: Ai Li Industrial
At the operation and maintenance site, we often encounter this problem: The HEPA pressure difference has increased, and it seems that it is just accumulated dust. Can it be removed, cleaned and continued to be used?
Direct answer: HEPA in ordinary clean rooms usually should not be washed, beaten or purged by itself and then reused directly. These operations may damage the filter material, edge sealing and sealing structure; whether regeneration is allowed must be based on the specific product description and project verification requirements.
This conclusion is not to deny all regeneration possibilities, but to remind: the efficiency, resistance and sealing status of the cleaned filter are difficult to judge by appearance.
The internal pleats and fiber structure of the filter make it difficult to judge its integrity based on appearance alone.
Even if the dust is reduced after cleaning, it cannot be inferred that the filtration efficiency, resistance and partial sealing still meet the original levels. Especially for glass fiber filter materials, once the pleats are squeezed or dampened, the local filtration path may change, and these changes are not visible on the surface. For adopting In the case of HEPA/ULPA air filters , the original grade of the product is supported by factory testing data, and the cleaning action itself will break this correspondence.
If the HEPA pressure difference rises too quickly, check the maintenance status of the primary and intermediate filters, the dust load at the inlet, moisture and system air volume.
Only dealing with the end filter element without checking the upstream cause may soon become clogged again. Supporting For the filter used in the FFU fan filter unit , it is also necessary to check whether the unit gear is adjusted higher - changes in air volume will also change the pressure difference reading, which may not necessarily mean that the filter element itself is clogged. Device-side applications such as The internal space of the EFU equipment-end fan filter unit is compact. Whether the inlet is close to the rack or cables may also affect the air inlet status.
When ordering a new filter element, you should check the efficiency level, rated air volume, outer frame size, sealing method and testing data.
After replacement, record the pressure difference reference and leak detection results. Do not use 'it looks normal after cleaning' as the only basis for putting it into use. If the liquid tank sealing structure is used at the original position, you need to check the matching status of the blade edge and the tank body when replacing it. Please refer to liquid tank seal HEPA ; if the original position is Interface description of For ULPA ultra-high efficiency filters , the testing data and on-site leak detection requirements should be rechecked according to the corresponding grade.
Purging or washing may damage the fold structure, glue lines and sealing materials, and it is often difficult to re-certify the performance of the entire product according to the original standards on site.
If the resistance increases, check the front-stage maintenance and inlet dust first; if it is necessary to replace it, check the spare parts according to the original interface specifications. For occasions with high production continuity requirements, rather than taking the risk of uncertain performance after cleaning, it is better to prepare spare parts according to the project maintenance plan to shorten downtime and replacement time.
project |
Confirmation method |
|---|---|
Product instructions |
Confirm whether regeneration is allowed and how |
Cause of blockage |
Check the front stage and inlet dust load |
New filter element specifications |
Check grade, air volume, frame and sealing |
Acceptance after replacement |
Record differential pressure reference and leak detection results |
Maintenance plans should be developed according to the installation location, pollution load and operation mode. The air volume and pressure difference after the new filter element is installed will be the benchmark for future comparisons; if the fan speed or front-stage filtration method is changed midway, it should be marked in the ledger to avoid misjudgment of service life.
If the pressure difference rises too fast multiple times at the same location, instead of repeatedly processing the terminal filter element, you should review the front-stage filtration configuration and on-site pollution sources. This type of systematic judgment is a matter of two levels, and a simple discussion of 'whether it can be washed'.
Aili Industrial can provide spare parts selection support based on the original HEPA model, installation interface and operating parameters. Keeping historical records of air volume and pressure difference can make the replacement plan more consistent with actual working conditions.
Aili Industrial produces HEPA/ULPA filters and supporting FFU fan filter unit , EFU and high-efficiency air supply outlet. When filters and air supply equipment are matched in the same system, spare parts specifications and interfaces can be uniformly checked at the ordering stage to reduce adaptation problems during replacement. For occasions such as semiconductors and pharmaceuticals that have high requirements for particle control, it is recommended to clarify in the project file whether the filter is allowed to be regenerated and the corresponding verification method.